pH controller PO 650 — installation and calibration

Aqua Filtration System, Faridabad · 9+ years in water treatment · Updated September 2026

Short answer: The PO 650 measures pH and can run a dosing pump through its relay. Three things matter for it to work properly — fitting the sensor away from the injection point, doing a proper two-point calibration, and setting a dead band so the pump does not switch on and off constantly.

Aster PO 650 pH and ORP controller
Aster PO 650 pH and ORP controller

PO 650 variants

ModelFeaturePrice
PO 350 IndicatorDisplay only, no relay₹7,035
PO 650 basicWith relay₹9,975
PO 650 high temp0-100°C sensor₹11,550
PO 650 tank applicationImmersed in a tank₹12,075
PO 650 SS Tri CloverFood and pharma fitting₹13,125
PO 650 auto temp compWhere temperature varies₹15,225
PO 650 ETPFor dirty water₹28,350

To send data to a panel or computer, a 4-20mA/RS485 output can be added for ₹3,360. Alternatively the blind pH transmitter (₹9,975) has no display and only sends a signal.

Where to fit the sensor — the critical point

The most common mistake: fitting the sensor right next to the chemical injection point. There the water is not yet mixed, so the sensor alternately reads far too high and far too low, and the controller behaves erratically.

The correct approach:

A practical arrangement: build a small bypass loop for the sensor with isolating valves. Then calibration does not require shutting the plant down — just close the loop and take the sensor out.

Installation step by step

  1. Mount the controller in a panel, away from sun and water, at eye level
  2. Fit the sensor tee into the line, usually 15NB or 20NB
  3. Run the cable — keep the sensor cable away from power cables, or noise will appear in the reading
  4. Apply power — the display should come on
  5. Calibrate (see below)
  6. Set the setpoint and dead band
  7. Wire the relay to the dosing pump
  8. Test — use buffer solution to confirm the pump starts and stops

Two-point calibration

  1. Remove the sensor, rinse with clean water, blot dry gently
  2. Place in buffer 7 and let it settle for a minute or two
  3. Enter calibration mode and set 7.00
  4. Rinse, then place in buffer 4 (for acid side work) or buffer 9.2 (for alkaline side)
  5. Set that value
  6. Refit the sensor

Which second buffer: use buffer 4 if you dose acid, and 9.2 if you dose alkali — the side you actually work on.

The full method is in our calibration guide.

Dead band — do not skip this

If your target is pH 7.0 and you simply set 7.0, the pump will start at 6.99 and stop at 7.01 — hundreds of times over. Both pump and relay will fail early.

So set a dead band: for example start at 6.8 and stop at 7.2. Now the pump only runs when it is genuinely needed.

ApplicationTargetDead band
ETP discharge7.06.7 – 7.3
RO feed (acid dosing)6.56.3 – 6.8
Swimming pool7.47.2 – 7.6
Boiler feed9.08.7 – 9.3

Wiring the relay to the pump

The PO 650 relay acts as a switch. Two approaches:

For dosing pumps see the Edose range — PVDF is essential for acid, as explained in our material guide.

Troubleshooting

ProblemLikely cause
Reading unstableSensor cable near a power cable, or no earthing
Always reads 7Sensor has failed
Calibration not acceptedSensor weak, or buffer expired
Pump switching on and off constantlyNo dead band set
pH not being controlledSensor too close to the injection point
Slow responseFilm on the sensor, or end of life

Maintenance schedule

Need help with a PO 650 setup?

Tell us your application and pH range, and we will recommend the right variant, sensor and dosing pump as a complete set.

📞 9910646957

Frequently asked questions

Where should a pH sensor be fitted?

At least ten to fifteen seconds of flow travel away from the chemical injection point, where the water is thoroughly mixed. Fitted too close, the sensor gives a false reading and the controller cannot work properly.

What is a dead band and why does it matter?

A dead band is a range, such as starting at six point eight and stopping at seven point two. Without it the pump switches on and off hundreds of times around the target value, which quickly wears out both pump and relay.

How often should a pH controller be calibrated?

At least once a month, using the two-point method with buffer seven followed by buffer four or nine point two. Calibration also tells you how the sensor is holding up.

What is the difference between PO 350 and PO 650?

The PO 350 only displays pH, while the PO 650 has a relay so it can operate a dosing pump. If you only need to see the reading the PO 350 is cheaper, but for automatic control you need the PO 650.

The reading is unstable — what should I check?

First check whether the sensor cable runs near a power cable, as that introduces noise. Then check the earthing, and confirm the sensor is not fitted too close to the injection point.