Automatic RO permeate diversion using a conductivity controller
Short answer: Using the relay on a conductivity controller you can make an RO plant look after itself — if permeate TDS rises, the plant stops or the water goes to drain, so poor quality water never reaches the tank. You need a CT 650 controller (₹5,880) and a solenoid valve.
Alternatively, take a ROMATIC controller (₹17,850), which has all of this built in.

The problem this solves
An RO membrane weakens gradually. One day permeate TDS starts rising — but the plant carries on running and the poor quality water goes straight into the tank.
You only find out when the whole tank is spoiled, or a customer complains. On larger plants this is a serious issue, particularly in packaged water and pharma.
The solution — automatic diversion
The controller continuously monitors permeate TDS. If it exceeds the set limit, the relay operates, and that relay can either:
- Stop the plant — the simplest option
- Send permeate to drain — the plant keeps running and the membrane keeps flushing (better)
- Sound an alarm — so somebody comes to look
What you need
| Item | Function | Price |
|---|---|---|
| CT 650 with relay | Monitors TDS and switches | ₹5,880 |
| Solenoid valve 20NB | Diverts the water | ₹3,360 |
| Rotameter | Flow indication | ₹578 |
| Total | Basic automatic control | ~₹9,800 |
Alternatively the ROMATIC controller (₹17,850) provides all of it in a single unit, with no wiring complications.
What setpoint to use
Set it somewhat above your normal reading — not too close, or the plant will keep diverting unnecessarily.
| Application | Normal permeate | Setpoint |
|---|---|---|
| Drinking water | 20–50 ppm | 80–100 ppm |
| Packaged water | 10–30 ppm | 50 ppm |
| Boiler feed | 5–20 ppm | 30 ppm |
| Industrial process | As required | 30% above requirement |
Where to fit the sensor
- On the permeate line, after the membrane and before the diverter valve
- Where flow is continuous
- Permanently immersed
- Easy to remove for cleaning
A meter on the feed line as well is better still, since that gives you rejection. The formula is in our TDS guide.
Startup flush — another useful benefit
For the first few minutes after an RO plant starts, permeate TDS is high, because standing water is being flushed out of the membrane. Automatic control handles this too:
- Plant starts — TDS high, valve to drain
- Within 2 to 3 minutes TDS falls
- The valve switches automatically to the tank
So only good water ever enters the tank, without anyone having to think about it.
Wiring points
- Check the relay rating — a small solenoid valve can be connected directly, but a larger load needs a contactor
- Keep the sensor cable away from power cables — otherwise the reading becomes unstable
- Normally open or normally closed — choose the valve so that on power failure the water goes to drain, not to the tank. This is a safety point
Where this setup is essential
- Packaged drinking water — quality cannot be compromised
- Pharma and food — validation and audit
- Large plants with big tanks — one bad batch spoils the whole tank
- Unmanned plants — nobody is watching
Where it is not needed
- Small plants where TDS is checked daily
- Where the end use is not sensitive to a modest rise in TDS
- Domestic RO systems
There a simple TDS meter (₹2,730) is sufficient — provided somebody makes a habit of looking at it.
Add automatic TDS control
Send your plant capacity and permeate TDS, and we will quote the complete set of controller and valve.
💬 WhatsApp par poochhein 📞 9910646957Frequently asked questions
How does automatic TDS control work on an RO plant?
A conductivity controller continuously monitors permeate TDS. When it exceeds the set limit, its relay operates a solenoid valve which sends the water to drain, so that poor quality water does not reach the storage tank.
Is it better to stop the plant or divert the water?
Diverting is better. Stopping the plant leaves water standing inside the membrane where bacteria can develop, whereas with diversion the plant keeps running and the water returns to the tank as soon as TDS is normal again.
What setpoint should be used?
Around thirty to forty percent above your normal permeate reading. Setting it too close means the plant will keep diverting unnecessarily. Always set a dead band as well so the valve does not keep cycling.
What position should the valve default to on power failure?
To drain. That ensures unchecked water does not enter the tank during a power cut. It is a small detail but an important safety consideration when selecting the valve.
Should I buy a ROMATIC or separate components?
The ROMATIC brings everything into one unit with no wiring complications, but costs more. Separate components are cheaper although the wiring has to be done correctly. For large or critical plants the ROMATIC is generally better.