Water test kits β SDI test kits (with filter papers) and hardness test kits β to check feed water before RO and monitor softener performance.
Live prices from our current price list. Click any product above for full specification, or ask us on WhatsApp.
Showing 4 of 4 products in this category. Prices exclusive of GST and subject to change — confirm before order.
Testing water takes five minutes and saves lakhs. Before designing any plant you need to know what is in the water; after commissioning, regular testing tells you whether the plant is still doing its job. We supply SDI test kits, hardness test kits and reagents for field and plant use.
A hardness kit gives you the calcium and magnesium content in ppm using a simple titration β you add drops of reagent to a measured water sample until the colour changes, and the number of drops gives the hardness. This is the number that decides softener sizing, and it is the number to check weekly on softener outlet. If treated water hardness starts climbing, regeneration or resin needs attention.
SDI (Silt Density Index) measures the fouling potential of feed water β how quickly it will clog a membrane. Water is passed through a 0.45 micron filter pad and the time taken is recorded at intervals. Membrane manufacturers typically require SDI below 5, and below 3 for long membrane life. If your membranes keep fouling despite good pre-treatment, an SDI test usually explains why.
For an RO plant: feed TDS and permeate TDS weekly, feed hardness weekly, SDI when commissioning or when fouling is suspected. For a softener: outlet hardness weekly. For an ETP or STP: pH, DO and settled sludge volume daily. Write the readings down. A trend over weeks tells you far more than a single reading, and auditors ask for records.
Complete test kits, refill reagents, SDI pads and measuring accessories. Delivery across Delhi NCR and pan-India, GST invoice on every order.
SDI shows how quickly water fouls a membrane; high SDI needs better pre-treatment. WhatsApp 9899193589 for the kit. Prices exclude GST.
A drop-count titration kit gives hardness in ppm to check softener performance.
Yes, SDI filter papers and hardness reagents are available separately.
Isi plant ke saath aksar ye bhi chahiye hota hai β ek hi jagah se, GST bill ke saath.
Apna number chhodein β hum aapko quotation ke saath call/WhatsApp karenge.